Despite the LEDs getting more and more efficient, big LED screens still consume a lot of power, and dealing with that and other power related issues isn’t trivial. Not everything is quite what it seems.

 

How much power do I need?

 

Manufacturers of LED screens typically state a maximum power consumption figure per panel or square meter as well as average power consumption, again per panel or square meter. Should you ‘play safe’ and assume the max power needed or is the average figure a better starting point?  Well that depends on your application and how adventurous you want to be!

First of all, keep in mind that both numbers are based on the screen running at full brightness. That is a very rare case. Most indoor screens are run at less than half brightness, sometimes even much lower than that.  Secondly, the max power consumption assumes all three colors at full brightness – in other words, a white image. Again, typically a very rare situation. But – you need to look at each application and project based on the use case, in some cases, LED screens are run at near full intensity (outdoor shows in daytime for example) and if there is a lot of white content (images), the power consumption will be quite high, potentially near max consumption.

But generally speaking, a fairly safe assumption is to use the average power consumption as guide for how many panels you can drive from a single supply socket. So let’s say your LED screen panels each draw 200W on average. 

Your power distribution uses 16A circuit breakers, so the max capacity is 16A x 230V = 3680W.  So capacity per channel is 3680 / 200 = 18.4 panels, or?

No, not quite – now we get to the challenges with inrush- and leakage currents!

Sneaky currents

 

LED screen panels use lightweight and highly efficient switch-mode power supplies. Clever technology that comes with two drawbacks;  they pull A LOT of current during a fraction of second when they are plugged in. Also, their design generates harmless but significant ‘background’ earth leakage current. These two issues is what really puts the limit on how many LED screen panels you can put on any given channel (and circuit breaker) in your power distribution.

The inrush currents is what forces you to turn on the circuit breaker several times before it stays in the ‘on’ position. Not good for the LED panel and not good for the circuit breaker.

Long cables tend to reduce this problem as the cable introduces a bit of resistance that limits the peak inrush current. The leakage current generated is a trickier problem. It’s highly recommended and in most case mandatory to have 30mA ‘earth leakage’ protection on supplies of 32A or less. 

However, an LED panel can easily generate as much as 2-3 mA of harmless background leakage and the “30mA” earth leakage breaker is allowed to cut the power already as 15mA!

Let’s assume 15mA and 3mA per panel – that’s max 5 panels per circuit breaker.

 

ledpanel backside

Conclusion

 

So as you can see, it is not the power consumption that limits the number of panels per circuit breaker, it is the inrush and leakage currents that sets the limits.

So, don’t be surprised if you end up needing more power distribution channels than what a calculation based on power consumption indicates.

If you’re fortunate enough to use a StageSmarts power distribution system, you will have a lot less issues with this. Our circuit breakers and earth leakage protection is far more tolerant against these inherent challenges.

 

Written by Mats Karlsson; CEO at Stage Smarts AB

You May Also Like…

Please don’t buy “a distro”

Please don’t buy “a distro”

Some people believe that all power distribution products are basically the same and that the choice comes down to price and availability. This is not correct. Some people also believe that if they buy a distro that conforms to all the relevant standards, then they have got the best possible protection. Again not correct. The published standards, whether international or national,

read more
Is the power distribution for your LED screen up to the job?

Is the power distribution for your LED screen up to the job?

Conventional power distribution will cheerfully pass 400V to the power supplies in your LED screen and at minimum, make the internal power supplies into scrap. Circuit breakers protect will only against over-currents, not over-voltages. This is a far too common problem. Equipment damage due to electrical faults is real and costs a lot

read more
So how did I end up here?!

So how did I end up here?!

It’s a common saying that people who work in the events services are usually failed DJs or failed musicians. There’s some truth in that. After giving up on the music career, I started helping other bands with sound and later lighting. So on the road, I went doing just about everything as one did back in the day (early 80’s). Fortunately, I had somehow managed to get a degree in electronics

read more

get in touch to find out more!

0 Comments

Submit a Comment

Your email address will not be published. Required fields are marked *

Connect with us

We’re always happy to discuss our services and products in more detail
Connect with us or give us a call on +46 40-16 32 63

.