Made to be on tour
The C72tv is a 72-channel power distribution unit, built for demanding production environments where safety, visibility and uptime are critical. Each channel is protected by a high performance 16A/30mA RCBO with C-type load trip characteristics and A-type earth leakage sensing.
These RCBOs are optimized for the tough load conditions that modern AV-equipment represents; inrush currents, significant leakage currents in particular. These circuit breakers combined overload, short-circuit and earth leakage protection in one compact unit that remains stable under all temperature conditions.
Our unique LoadSens system monitors every channel in real time. The front panel clearly indicates whether a channel is without a load, drawing current or is being overloaded. This makes fault finding fast and easy. All channel and system data is accessible via the integrated web server. This includes per-channel load current, incoming supply voltage and currents, system temperature and more, all available to you both locally and remotely.
Keyfeatures
- 72 channels each protected by a 16A/30mA RCBO.
- Powerlock 400A mains power input and pass-through.
- 6+1 single phase auxiliary channels each protected by a 16A/30mA RCBO.
- 3 x 3-phase socket (16-63A) each with breaker and fully adjustable earth-leakage protection
- Comprehensive real-time supervision of all in- and outgoing power
- Integrated web-server for remote supervision.
- Fast-acting over-voltage protection.
- Emergency stop button
- Wide range of output connector options.
- Wheeled flightcase with truck-pack friendly dimensions.
Tested, certified & documented
All of our products are thoroughly tested, certified and designed to meet or exceed all relevant standards. We provide manuals, drawings and technical documents to support you and your team whether you’re on tour, working on an installation or doing one-off gigs.Specifications
Feature | Value |
---|---|
Power input | Powerlock 400A 5-wire (TN-S) 230/400V |
Main breaker | MCCB, electronic protection, 4-pole 400A |
Over voltage protection | Immediate disconnection in case of a lost or weak neutral connection |
Main input metering | All incoming voltages,l currents (including neutral current), power factor, and mains frequency |
Main status indicators | Multicolored status indicator |
Channel load monitoring | Individual status indication for each channel via multicolor LED indicator |
No. of of main channels | 72 |
Channel capacity and protection | 16A / channel, RCBO A-type, 30mA |
Auxiliary capacity and protection | 16A-63A, 4-pole breaker, adjustable and switchable RCD (30mA-5A) (20ms-5s) |
Auxiliary channels X1-X6 | 16A (or 32A) / channel, RCBO A-type, 30mA |
Auxiliary channels X7-X9 | 16A-63A, 5-pin CEE |
Main output connections | Interchangeable output modules (per 24 channels) |
Worklight power sockets | 4 x 3-pole XLR, 12VDC, 15W, PWM dimmer |
USB-charger socket | 5VDC, 2.1A |
Dimentions and weight | 1342 x 600 x 723mm, 150kg |
Downloads
- Linedrawing C72tv – OPM True1 24xDownloadStorlek: 42.05 KB
- Linedrawing C72tv – OPM Socapex A 8xDownloadStorlek: 69.3 KB
- Linedrawing C72tv – OPM Socapex A 4xDownloadStorlek: 41.85 KB
- Linedrawing C72tv – OPM HA248 A 3xDownloadStorlek: 40.22 KB
- Linedrawing C72tv – OPM HA166 A 8xDownloadStorlek: 70.82 KB
- Linedrawing C72tv – OPM HA166 A 4xDownloadStorlek: 46.47 KB
- C72tv FolderDownloadStorlek: 1.83 MB
- C-series folderDownloadStorlek: 3.06 MB
- HMI application – WindowsDownloadStorlek: 131.46 MB
- HMI application – macOSDownloadStorlek: 116.48 MB
What can we help you with?
We are convinced that our products will serve you well but sometimes it can be hard to find the right model to serve your needs.